grokkingstuff Home Blog Projects Wiki Calculators About

Smoke control systems (NFPA 92)

modified2026-07-21statusfinished

NFPA 92 Standard for Smoke Control Systems §4.4 & §5.5 — atrium plume mass flow, exhaust sizing, and stairwell/door pressurization checks, in one reference.

Index

Each relation set below includes a Voici11Voici compiles a notebook to a static, serverless dashboard — mocked here as a static page, since this pipeline has no Jupyter kernel to run against. dashboard: a matplotlib-styled chart with the live calculator input marked as a red point on the curve.

1.1 · Axisymmetric plume mass flow

[1.1] Governing equations

$$\dot{m}_p = 0.071\,\dot{Q}_c^{1/3} z^{5/3} + 0.0018\,\dot{Q}_c \quad (z \ge z_l)$$

$$z_l = 0.166\,\dot{Q}_c^{2/5}$$

$\dot{m}_p$ smoke mass flow (kg/s), $\dot{Q}_c$ convective HRR (kW), $z$ clear layer height (m). Source: NFPA 92 §5.5, SFPE Handbook.

z (clear height) z_l (virtual origin) design fire, Q̇c smoke layer, ṁp
FIG. 01 — axisymmetric plume geometry: virtual origin z_l, clear height z
reference photo — atrium fire plume / smoke layer (NFPA 92 Fig. 5.5.1 or similar)
REF. — drop in a real photo here to validate FIG. 01 against

1.2 · Balcony spill & window plume

[1.2] Governing equation

$$\dot{m}_p = 0.36\left(z+z_b\right)^{1/3} W \dot{Q}_c^{1/3}$$

$W$ balcony width (m), $z$ height above balcony (m), $z_b$ balcony height above fire source (m). Source: NFPA 92 §5.5.

z (above balcony) z_b W
FIG. 03 — smoke spilling under a balcony/overhang into an atrium void
reference photo — balcony spill plume / atrium void opening
REF. — drop in a real photo here to validate FIG. 03 against

1.3 · Volumetric smoke exhaust & density correction

[1.3] Governing equations

$$T_s = T_0 + \frac{\dot{Q}_c}{\dot{m}_p c_p},\quad \rho_s = \rho_0\frac{T_0}{T_s},\quad V_e = \frac{\dot{m}_p}{\rho_s}$$

$c_p \approx 1.0\ \text{kJ/kg·K}$. Converts smoke mass flow to fan volumetric duty. Source: NFPA 92 §5.5.

Smoke temp Ts
Smoke density ρs
Volumetric rate Ve

1.4 · Plugholing limit

[1.4] Governing equation

$$V_{\text{max}} = 3.3\,\gamma\, d^{5/2}\left(\frac{T_s-T_0}{T_0}\right)^{1/2}$$

$\gamma$ location factor (1.0 center of layer, 0.5 near a wall/perimeter). Prevents clean air pull-through at a single exhaust inlet. Source: NFPA 92 §5.5, NFPA 204.

exhaust inlet plughole (clean air pulled up) d clean air layer
FIG. 05 — smoke layer depth d at a single point extract; plugholing draws clean air through the layer
reference photo — smoke exhaust inlet / plugholing vortex at ceiling vent
REF. — drop in a real photo here to validate FIG. 05 against

1.5 · Stairwell pressurization airflow

[1.5] Governing equation

$$Q = C\,A_e\sqrt{\frac{2\Delta P}{\rho}}$$

Target overpressure 0.05–0.10 in. w.g. (12–25 Pa) per NFPA 92 §4.4. $A_e$ total leakage area, $C$ flow/discharge coefficient (~0.6 for cracks). Source: NFPA 92 §4.4.

pressurized stair fire floor leakage, Ae, ΔP supply fan, Q
FIG. 07 — stairwell pressurization: supply air leaks through door/crack area at target ΔP
reference photo — stairwell pressurization fan / egress stair door
REF. — drop in a real photo here to validate FIG. 07 against

1.6 · Door opening force

[1.6] Governing equation

$$F = F_{dc} + \frac{W\cdot A\cdot\Delta P}{2(W-d)}$$

Egress doors must open at $F \le 133\,\text{N}$ (30 lbf) per NFPA 101. $F_{dc}$ closer force, $W$ door width, $A$ door area, $d$ knob offset from hinge edge. Source: NFPA 92 §4.4, NFPA 101.

hinge knob, d from edge F stair side, ΔP W
FIG. 09 — pressure differential across an egress door increases the force needed to swing it open
reference photo — egress door closer / knob with pressure-differential test rig
REF. — drop in a real photo here to validate FIG. 09 against